An Experience of Ageing on XLPE Insulation

Authors

  • W. G. Ariastina Department of Electrical Engineering, Udayana University, Bali-80362, Indonesia
  • A. I. Weking Department of Electrical Engineering, Udayana University, Bali-80362, Indonesia
  • I. N. S. Kumara Department of Electrical Engineering, Udayana University, Bali-80362, Indonesia
  • I. A. D. Giriantari Department of Electrical Engineering, Udayana University, Bali-80362, Indonesia
  • I. N. Sugiarta PT PLN (Persero) Distribution of Bali, South Bali Network Area, Bali-80113, Indonesia

DOI:

https://doi.org/10.11113/jt.v64.2093

Keywords:

XLPE insulation, ageing, partial discharges

Abstract

A case study of ageing on XLPE conductor insulation of 20kV primary distribution feeder is presented in this paper. The insulation degradation mainly occurred around conductor tie where the conductor is attached to the post insulator. A section of distribution feeder with defects on the conductor insulation has been examined for this study. Potential losses due to presence of discharges have been investigated by measuring the difference current at locations of the affected conductor. Temperature measurements of the insulation surface have also been carried out. Provisional maintenance procedures were introduced to eliminate the discharges. Measurements of current and surface temperature were repeated nine months after completion of the maintenance work. Results indicated that the discharges have been completely disappeared.

References

PT. PLN (Persero). 1981. PLN Standard 41-8-1981: All Aluminium Alloy Conductor. Jakarta (in Indonesian).

PT. PLN (Persero). 1991. PLN Standard 41-10-1991: All Aluminium Alloy Conductor-Sheathed. Jakarta (in Indonesian).

PT. PLN (Persero). 1981. PLN Standard 39-1-1981: Power Cable Test. Jakarta (in Indonesian).

Sugiarta, I N. 2011. A Study of Partial Discharge Phenomena on AAAC-S Conductor Ties in East Bali 20kV Distribution Network. Denpasar: Udayana University.

Garton, A., S. Bamji, A. Bulinski and J. Densley. 1987. Oxidation and Water Tree Formation in Service-Aged XLPE Cable Insulation. IEEE Trans. E. I. EI-22(4): 405–412.

Mashikian, M. S. and A. Szatkowski. 2006. Medium Voltage Cable Defects Revealed by Off-Line Partial Discharge Testing at Power Frequency. IEEE E. I. Mag. 22(4): 24–32.

Montanari, G. C., A. Cavallini, F. Puletti, 2006. A New Approach to Partial Discharge Testing of HV Cable Systems. IEEE E. I. Mag. 22(1): 14–23.

Li, J., et al. 2011. The Effect of Accelerated Water Tree Ageing on the Properties of XLPE Cable Insulation IEEE Trans. D. E. I. 18(5): 1562–1569.

Metwally, I. A. 2012. The Evolution of Medium Voltage Power Cables. IEEE Potentials. May/June. 20–25.

Li, W., et. al. 2012. Frequency Dependence of Breakdown Performance of XLPE with Different Artificial Defects. IEEE Trans. D. E. I. 19(4): 1351–1359.

Nóbrega, A. M., M. L. B. Martinez, A. A. A de Queiroz. 2013. Investigation and Analysis of Electrical Aging of XLPE Insulation for Medium Voltage Covered Conductors Manufactured in Brazil. IEEE Trans. D. E. I. 20(2): 628–640.

Downloads

Published

2013-09-15

Issue

Section

Science and Engineering

How to Cite

An Experience of Ageing on XLPE Insulation. (2013). Jurnal Teknologi, 64(4). https://doi.org/10.11113/jt.v64.2093