Thermal Image and Leakage Current Diagnostic as a Tool for Testing and Condition Monitoring of ZnO Surge Arrester

Authors

  • Novizon N. Electrical Engineering, University of Andalas (UNAND), Indonesia
  • Zulkurnain Abdul Malek IVAT Electrical Engineering, Universiti Teknologi Malaysia, 81310 UTM Johor Bahru, Johor, Malaysia
  • Nouruddeen Bashir IVAT Electrical Engineering, Universiti Teknologi Malaysia, 81310 UTM Johor Bahru, Johor, Malaysia
  • N. Asilah IVAT Electrical Engineering, Universiti Teknologi Malaysia, 81310 UTM Johor Bahru, Johor, Malaysia

DOI:

https://doi.org/10.11113/jt.v64.2096

Keywords:

Zinc oxide arrester, leakage current, thermal image, artificial neural network

Abstract

This paper presents a study proposing a method to assess the condition of metal-oxide surge arresters. Thermal data using thermal imaging as well as the leakage current third harmonic component were used as tools to investigate the surge arrester aging condition.  Artificial Neural Network was employed to classify surge arrester condition with the temperature profile, ambient temperature and humidity as inputs and third harmonic leakage current as target. The results indicated a strong relationship between the thermal profile and leakage current of the surge arrester. This finding suggests the viability of this method in condition monitoring of surge arrester.

References

A. K. S. Jardine, et al. 2006. A Review on Machinery Diagnostics and Prognostics Implementing Condition-based Maintenance. Mechanical Systems and Signal Processing. 20: 1483–1510.

Z. Tian, et al. 2009. Condition Based Maintenance Optimization Considering Multiple Objectives. Journal of Intelligent Manufacturing. 1–8.

T. Tada, et al. 2002. A Diagnosis Of Remaining Life Characteristics Of Zno Type Surge Arresters (1st stage) for 275 kV Power Systems. In Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES. 3: 2233–2238.

X. Chen, et al. 2008. Research of Infrared Diagnosed of Faults of Arrester. In High Voltage Engineering and Application. ICHVE 2008. International Conference. 637–640.

C. A. Christodoulou, et al. 2009. Measurement of the Resistive Leakage Current In Surge Arresters Under Artificial Rain Test and Impulse Voltage Subjection. Science, Measurement & Technology, IET. 3: 256–262.

C. A. Laurentys Almeida, et al. 2009. Intelligent Thermographic Diagnostic Applied to Surge Arresters: A New Approach. Power Delivery, IEEE Transactions. 24: 751–757.

J. Jun and W. Yu. 2010. Research on Online Monitoring of Arrester. In 2010 China International Conference on Electricity Distribution, CICED 2010, September 13, 2010 - September 16, 2010, Nanjing, China,

C. Srisukkhom and P. Jirapong. 2011. Analysis of Electrical and Thermal Characteristics of Gapless Metal Oxide Arresters Using Thermal Images. In Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), 2011 8th International Conference. 677–680.

E. T. Wanderley Neto, et al. 2006. Monitoring and Diagnosis of ZnO Arresters. Latin America Transactions, IEEE (Revista IEEE America Latina). 4: 170–176.

Z. Abdul-Malek, et al. 2008. A new Method to Extract the Resistive Component of the Metal Oxide Surge Arrester Leakage Current. In Power and Energy Conference, 2008. PECon 2008. IEEE 2nd International. 399–402.

B.-H. Lee and S.-M. Kang. 2005. A New on-line Leakage Current Monitoring System of ZnO Surge Arresters. Materials Science and Engineering B. 119: 13–18.

E. T. W. Neto, et al. 2004. Electro-thermal Simulation of ZnO Arresters for Diagnosis Using Thermal Analysis. In Transmission and Distribution Conference and Exposition: Latin America, 2004 IEEE/PES. 338–343.

K. L. Wong, et al. 2004. Emission-based Condition Monitoring Technique for ZnO Surge Arrester. In Proceedings of the Seventh IASTED International Conference on Power and Energy Systems, November 28, 2004 - December 1, 2004, Clearwater Beach, FL, United states. 234–237.

C. Karawita and M. R. Raghuveer. 2006. Onsite MOSA Condition Assessment-A New Approach. Power Delivery, IEEE Transactions. 21: 1273–1277.

E. T. W. Neto, et al. 2006. Failure Analysis in ZnO Arresters Using Thermal Images. In Transmission & Distribution Conference and Exposition: Latin America, 2006. TDC '06. IEEE/PES. 1–5.

W. Zhou, et al. 2008. Design of On-line Monitoring Device for MOA used in 10kV Distribution Network. In Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference. 407–411.

J. Lundquist, et al. 1990. New Method for Measurement of the Resistive Leakage Currents of Metal-Oxide Surge Arresters in Service. Power Delivery, IEEE Transactions. 5: 1811–1822.

S.-B. Lee, et al. 2010. Analysis of Thermal and Electrical Properties of Zno Arrester Block. Current Applied Physics. 10: 176–180.

C. A. L. Almeida, et al. 2005. Intelligent Detection and Diagnosis of Lightning Arrester Faults Using Digital Thermovision Image Processing Techniques. Orlando, FL, USA. 109–120.

C. Ying-Chieh and L. Yao. 2009. Automatic Diagnostic System of Electrical Equipment Using Infrared Thermography. In Soft Computing and Pattern Recognition, 2009. SOCPAR '09. International Conference. 155–160.

Z. Abdul-Malek, et al. 2008. Portable Device to Extract Resistive Component of the Metal Oxide Surge Arrester Leakage Current. In Power Engineering Conference, 2008. AUPEC '08. Australasian Universities. 1–5.

L. Huijia and H. Hanmei, 2010. Development of Tester of the Resistive Leakage Current of MOA. In Power and Energy Engineering Conference (APPEEC), 2010 Asia-Pacific. 1–4.

A. Gakiya Kanashiro, et al. 2011. Diagnostic of Silicon Carbide Surge Arresters Using Leakage Current Measurements. Latin America Transactions, IEEE (Revista IEEE America Latina). 9: 761–766.

C. Yang, et al. 2008. Infrared Technology in the Fault Diagnosis of Substation Equipment. In Electricity Distribution, 2008. CICED 2008. China International Conference. 1–6.

Z. Azmat and D. J. Turner. 2005. Infrared Thermography and Its Role in Rural Utility Environment. In Rural Electric Power Conference. B2/1–B2/4.

L. Baoshu, et al. 2006. HV Power Equipment Diagnosis Based on Infrared Imaging Analyzing. In Power System Technology, 2006. PowerCon 2006. International Conference. 1–4.

L. Huangqiang, et al. 2009. Research on HV-Power Equipment Diagnosis by Infrared Image Edge Detection," in Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific. 1–4.

Z. Korendo and M. Florkowski. 2001. Thermography Based Diagnostics of Power Equipment. Power Engineering Journal. 15: 33–42.

H. Niancang. 1998. The Infrared Thermography Diagnostic Technique of High-Voltage Electrical Equipments with Internal Faults. In Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference. 1: 110–115.

Baran, et al. 2010. Thermographic Diagnostic of Electrical Machines. In Electrical Machines (ICEM), 2010 XIX International Conference. 1–3.

S. Stipetic, et al. 2011. Measurement of Excitation Winding Temperature on Synchronous Generator in Rotation Using Infrared Thermography," Industrial Electronics, IEEE Transactions. 1–1.

E. C. Bortoni, et al. 2010. Hydro Generator Efficiency Assessment Using Infrared Thermal Imaging Techniques. In Power and Energy Society General Meeting, 2010 IEEE. 1–6.

M. Muhr, et al. 2006. Thermography of Aged Contacts of High Voltage Equipment. Elektrotechnik und Informationstechnik. 123: 537–543.

L. dos Santos, et al. 2008. Infrared Thermography Applied for Outdoor Power Substations. Orlando, FL, USA. 69390R–11.

Downloads

Published

2013-09-15

Issue

Section

Science and Engineering

How to Cite